SDM-IO16 16 Channel Input/Output Expansion Module
; Call instruction 188 to set the ports up
2: SDM-IO16 (P188)
1: 00 SDM Address
2: 90 Command Code Option
3: 4444 Ports 16-13 ;configure the ports
4: 4444 Ports 12-9 ;Set so all ports will cause an interrupt
5: 4444 Ports 8-5
6: 4444 Ports 4-1
7: 1 Return Code Loc [ Errcount ] ;for return code
8: 2 First Loc [ Portstat_]
9: 1.0 Mult
10: 0.0 Offset
;Set flag 1 high to indicate we have run the setup code
3: Do (P86)
1: 11 Set Flag 1 High
4: End (P95) ; of IF block
;Now the rest of the other normal measurements would follow
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
;Subroutine 98 will be run when a signal is generated by the I/O line
;from the IO16 connected to C8 on the datalogger.
1: Beginning of Subroutine (P85)
1: 98 Subroutine 98
;First read the port status from the IO16 as quickly as possible
;The speed at which the datalogger can respond to the I/O signal will
;determine the minimum pulse width that you can guarantee to capture
;as a change of state of a port. Typically this will be 10 ms but will
;vary with the datalogger and other activity.
;Reading the port status will cancel further polling
;until the next change of state.
2: SDM-IO16 (P188)
1: 00 SDM Address
2: 91 Command Code Option ;read the port status into one location
3: 0 Ports 16-13 ;port settings not used for code 91
4: 0 Ports 12-9
5: 0 Ports 8-5
6: 0 Ports 4-1
7: 1 Return Code Loc [Errcount ] ;for return code
8: 2 First Loc [Portstat ]
9: 1.0 Mult
10: 0.0 Offset
27