AL200 ALERT2 Encoder, Modulator, and Sensor Interface
Set the Sensor Scan IntervalThis is how often the AL200 will
power up and measure attached and enabled sensors. Value is
expressed in seconds.
Set the SW12 Warm Up TimeThis is the amount of time in
seconds that the AL200 will wait after powering up attached sensors
before making a measurement.
Set the P1 ModeEnable or disable the pulse count channel
depending on whether or not it is being used.
Set the SE1 ModeSet to Millivolt if using a sensor that has a single
ended voltage output. Set to Milliamp if sensor has a single ended
current output or 4-20 mA loop output.
Set the SE1 ALERT2 Sensor IDThis is the sensor ID of the sensor
connected to the SE1 channel. See Appendix G, List of
Recommended Sensor IDs, for a list of recommended sensor ID
values.
Set the SE1 MultiplierThis is a sensor specific value that along
with the SE1 Offset will be used to convert the analog output of a
sensor to an engineering unit. See Appendix H, Calculating
Multipliers and Offsets, for how to calculate multipliers and offsets.
Set the SE1 OffsetThis is a sensor specific value that along with the
SE1 Multiplier will be used to convert the analog output of a sensor to
an engineering unit. See Appendix H, Calculating Multipliers and
Offsets, for how to calculate multipliers and offsets.
Set the SE1 Tx ChangeThis is the threshold which a calculated
value for the SE1 measurement must exceed in order to trigger a data
transmission.
Set the C1 ModeSet to Status to configure C1 to read a dry contact
(commonly a float switch). Set to SDI-12 to configure for use with an
SDI-12 type sensor.
Set the C1 ALERT2 Sensor IDThis is the sensor ID of the sensor
connected to the C1 channel. See Appendix G, List of Recommended
Sensor IDs, for a list of recommended sensor ID values.
Set the SDI-12 CommandThis is the measurement command that
will be sent to the attached SDI-12 sensor. The format is xM!, where
x is the SDI-12 address.
Set the SDI-12 Value to SendIf the attached SDI-12 sensor returns
more than one value, select which value will be used.
Set the SDI-12 Multiplier (1) This is a sensor specific value that
along with the SDI-12 Offset will be used to convert the analog output
of a sensor to an engineering unit. See Appendix H, Calculating
Multipliers and Offsets, for how to calculate multipliers and offsets.
(Note that most SDI-12 sensors do not require a multiplier or offset
except for unit conversion.)
11