Section 4. Communication
Programming Examples
The following example allows the CR1000 to communicate with one
CSBUOY-DT.
‘CR1000 Series Datalogger
Public Result, Remotedata (3)
DataTable (Test,1,-1)
DataInterval (0,60,Sec,10)
Sample (3,Remotedata(),FP2)
EndTable
Alias Remotedata(1) = DOmV
Alias Remotedata(2) = WaterTempC
Alias Remotedata(3) = BatteryVolt
BeginProg
Scan (30,Sec,0,0)
GetVariables (Result,ComSDC7,0,1,0000,0,“Public”,“Buoydata()”,Remotedata(),3)
‘where 1 is the PakBus address of the CSBUOY-DT
CallTable Test
NextScan
EndProg
This example allows the CR10X to communicate with one CSBUOY-DT.
;{CR10X-PB}
;
*Table 1 Program
01: 30 Execution Interval (seconds)
1: Batt Voltage (P10)
1: 1 Loc [ Batt ]
2: PakBus - Wireless Network Master (P193)
1: 1 Number of Remotes
2: 10 First Remote Address
3: 0 Time Into Transmit Interval (sec)
4: 300 Transmit Interval (sec, 0 = use execution interval)
5: 0 Transmit Delay Between Remotes (sec)
6: 5 Swath to Receive
7: 7 First Loc for Data Received [ RID_1 ]
8: 0 Swath to Send
9: 18 First Loc to Send [ Scratch ]
10: 2 Result Code Loc [ RCom_1 ]
3: Data Table (P84)
1: 0 Seconds into Interval
2: 300 Seconds Interval
3: 0 (0 = auto allocate, -x = redirect to inloc x)
4: Hist Table Name
4-2
Commenti su questo manuale