Section 8. Operation
351
Command 6 Copies the specified program to the designated drive and sets
the run attribute of the program to Run Now. Data on a CF card from the
previously running program will be preserved.
Command 7 Copies the specified file to the designated drive with no run
attributes.
Command 13 Copies the specified program to the designated drive and sets
the run attribute of the program to Run Always. Data on a CF card from the
previously running program will be erased.
Command 14 Copies the specified program to the designated drive and sets
the run attribute to Run Now. Data on a CF card from the previously running
program will be erased.
Example Power-up.ini Files
Powerup.ini Example
'Code format and syntax
'Command = numeric power-up command
'File = file associated with the action
'Device = device to which File is copied. Defaults to CPU:
'Command,File,Device
13,Write2CRD_2.cr1,cpu:
Powerup.ini Example
'Copy program file pwrup.cr1 from the external drive to CPU:
'File will run only when CR3000 powered-up later.
2,pwrup.cr1,cpu:
Powerup.ini Example
'Format the USR: drive
5,,usr:
'
Powerup.ini Example
'Load an operating system (.obj) file into FLASH as the new OS.
9,CR3000.Std.04.obj
Powerup.ini Example
'A program file is carried on an external USB: drive.
'Do not copy program file from USB:
'Run program always, erase data.
13,toobigforcpu.cr1,usb:
Powerup.ini Example
'Run a program file always, erase data.
13,pwrup_1.cr1,cpu: